Messages and Diagnostics
SIWAREX FTA
No.
command errors -
Interface
parameter error
permitted for
The baud rate for the RS232 interface is not permitted. Define
the baud rate.
assignment or
process value
assignment
The assignment of the process alarm or the process values in
DR7 for the S7 interface is incorrect. Change your assignment.
Baud rate not
defined for RS485
The baud rate for the RS485 interface is not defined. Define the
baud rate.
possible since
be executed, since
MMC is defective or
Trace recording
cycle too small
The trace cycle in DR7 is too short. Define parameters for
a longer trace cycle (for MMC minimum 5 x 10 msec).
The log text with the fill parameters is too long of the end
character (EOT) is missing. Change the log text.
Ensure that the proper number of characters for the
corresponding field are used in place of the respective print field
code. The overall length of the text filled with values may not
exceed 160 characters (including printer control character but not
fields that are not
Log text contains fields that are not permitted Change the log
text.