Messages and Diagnostics
SIWAREX FTA
7-148
Error
No.
Data and
command errors -
description
Solution
149
Start not possible
since the
distribution memory
1 can overflow
Start not possible since the totalising of actual values in
distribution memory 1 overflowed in calibratable operation
(Specifications Code OIML in DR 3). Evaluate the distribution
memory and them delete them.
150
Command
impossible since
SIMATIC CPU is in
STOP
The command can only be executed in SIMATIC CPU RUN status.
This applies for the following commands (Codes):
Start a dosing procedure (100, 101, 102)
Step-on (103, 104)
Residual weighing (110)
Emptying on/off (109, 118)
151
Reserved
152
Reserved
153
Reserved
154
Reserved
155
Reserved
156
Reserved
157
Reserved
158
Reserved
159
Reserved
160
Reserved
161
Reserved
162
Reserved
163
Reserved
164
Reserved
165
Reserved
166-
175
Number format
error in data
record
166
Date Time
implausible
Data and time definition not plausible.
Correct the definition.
The following are allowed:
Year: 0..99
Month: 1..12
Day: 1..28/29/30/31
(depending on the month)
Hours: 0..23
Minutes: 0..59
Seconds: 0..59
Weekday: 1..7
167
Time definition
implausible
The definition for a time definition is not plausible. Check the
following conditions:
DR3: Standstill times 1, 2 or 3 must be at least 100 msec
DR4: Timeout value for the log output monitor must be at least
1000 msec
DR23: Inching time must be greater than 0
DR23: The emptying time may not be greater than the maximum
emptying time
168
Default percentage
value > 100%
The percentage definition is greater than 100%. Decrease one of
the following entries.