Messages and Diagnostics
SIWAREX FTA
7-149
Error
No.
Data and
command errors -
description
Solution
DR3: Maximum weight for zero setting and zero setting (pos. /
neg.) and tare max. load
DR7: Sum of memory segment for trace function and log function
DR23: Default value for analog output (Coarse, Fine)
DR23: Control factor Fine time controller
DR23: Control factor Proportional controller
169
Negative default
value not permitted
Negative default value not permitted. Change the entry.
The following values may not be negative:
DR 3:
Adjustment weight 1..4
Numeral steps 1..3, Total numeral step
Standstill value 1..3
Transfer-Minimum weight
DR 15:
Tare default value
DR 20:
Set value
DR 21:
Loading quantity
DR 22:
Tolerance limits TU1, TU2, TO1, TO2
DR 23:
Max. Single fill
Maximum controller access
Controller optimum plus/minus
170
Number range for
weighing values
exceeded
The number range of a definition is not permitted. The following
values must be larger -100 000 000 and less than 100 000 000:
DR3:
Adjustment weight 1, 2, 3 or 4
Minimum, maximum weight and numeral step of weighing range
1, 2 or 3
Standstill range 1, 2 or 3
Smallest set weight and distribution value (in addition, the lowest
set weight must be greater than or equal to the minimum weight
for weighing range 1)
DR4:
Empty range
Switch on or shut-off weight of limit value 1, 2 or 3
DR7 - Analog output:
Weight for zero value, End value
Replacement value
DR15: Tare definition
DR16: Weight simulation definition
DR20: Set value
DR22: (All weights in addition < Maximum weighing range + 9
weighing steps)
Trailing weight
Fine weight
Shut-off correction value
TO1, TO2, TU1, TU2
DR23:
Max. Single set value