Messages and Diagnostics
SIWAREX FTA
7-150
Error
No.
Data and
command errors -
description
Solution
Max. Single controller access
Controller Optimum Plus/Minus
171
Checksum error
Checksum error in data record 26 or 27.
The data was falsified or the DR versions do not match.
172
Selection code
unknown
In the parameters, there is a number for selecting a characteristic
which has no meaning. The following values must be retained:
DR3:
Source for weight simulation 0..2
Decade for the curve 0..6
Source for the analog output 0..4
DR23:
Filter type 0..2
Limit frequency Filter 0..9
Tare-/Zero setting mode 0..4
Controller type selection 0..3
173
Reserved
174
Reserved
175
Reserved
176-
177
Impedance error
176
Impedance error
Impedance error is generated if the deviation in impedance is
greater than 10 % of the reference value or if an error has
occurred in the measurement
178-
199
General data and
command errors
178
DS writing not
possible
You cannot write to the selected data record if write protection is
set.
179-
199
Reserved
Table 7-1 List of Data and Operating Errors