Messages and Diagnostics
SIWAREX FTA
7-153
Error
No.
Technology message - description
Solution
28
Reserved
29
Reserved
30
Reserved
31
Reserved
32
Reserved
33
Reserved
34
Reserved
35
Reserved
36
Reserved
37
Reserved
38
Reserved
39
Reserved
40
Reserved
41-100
Error in the weighing cycle
41
Timeout step switching
Step-on to next weighing step has not
occurred within the time defined in DR23.
42
Inhibition time violation coarse
After the coarse inhibition time has elapsed or
during the inhibition time set/actual
comparison, the fine shut-off point was
exceeded.
43
Inhibition time violation fine
After the fine inhibition time has elapsed or
during the inhibition time set/actual
comparison, the fine shut-off point was
exceeded.
44
Weighing time exceeded
Weighing procedure not completed within the
weighing time defined in DR22.
45
Empty time exceeded
Emptying was not completed within the
weighing time defined in DR23.
46
Weighing procedure stopped, range
exceeded for zero setting or with taring
The weighing procedure was stopped
because zeroing or zero setting or taring was
not possible.
Gross outside of zero setting range
Tare maximum load exceeded
Current gross weight is less than the minimum
tare weight defined in DR 23.
47
Control range exceeded
The determined manipulated variable of the
Proportional- or fine time controller is greater
than the maximum one-time control access
defined in DR 23. Depending on the definition
of the control behavior for scale faults in
DR23, no control is performed in this case or
the manipulated variable is limited to the
maximum control access value.
48
Weighing stopped because of CPU stop
A dosing operation that is currently running is
stopped if the S7 CPU goes into Stopped
state.
49
Weighing stopped because of dosing
error
A dosing fault leads to implausible shut-off
points for coarse and fine feeds.