4.3 Operating access
Notes
operating ACCESS: via PASSWORD, password consists of 4 digits
The 4 basic passwords can be programmed individually by the service engineer
After 3 consecutive incorrect password entries the operating access is disabled for 15
minutes
operating ACCESS: via KEY SWITCH (user 1), can also be made accessible if optional
key lock switch (Z3S020/030) is supplied
Editing of user text / Service functions (user 2) can be made available to the ’user 2’ if
required (by telling the password to the operator)
Individual password forgotten: Set system to the default password
Procedure: (Press reset key ”S2” (master board) and concurrently press key ”S1” for system restart (keep
”S2” pressed until the system start is completed (see below) / user data remain unchanged)
INITIATION mode: 1. restart
2. autom. config.
system BLOCKED
Overview of the access levels
Access level
Default
password
Group of persons Enabled operating functions
User operating everybody
− Scrolling alarm messages
− Acknowledge messages
User operating
0055
(or key-lock)
(User 1)
system operator
− Acknowledge messages
− Alarm reset
− Fault / Info scrolling
− Isolation of system parts
− Poll system information
− Perform system tests
Editing of
user text
0011
(User 2)
service engineer
− Edit user text
Service /
Maintenance
0033
(User 2)
service engineer
− Service functions
− Erase data
Configuration
8642
service engineer
− Application setting
− Setting passwords
Configuration
8642
service engineer
− Application setting
− Setting passwords
Remark: command ’Acknowledge messages’ with programmable operating access either ’always’ or via
level ’user 1’
Automatic timeout
The access by password is automatically cancelled if no key is operated for
a) 5 min during state ’normal operation’
b) 30 sec during condition ’alarm’