7-1
{xe "service port"}
The 4100ES supports IDNet ports on several different slave cards. Each IDNet port
provides a connection to a wiring loop of up to 250 addressable detectors and devices.
These IDNet ports use Mapnet Protocol and communicate with existing Mapnet
detectors/devices plus the new IDNet devices.
The 4100ES slave modules with IDNet ports are:
4100-9848AU SPS System Power Supply
4100-3101AU IDNet card
4100-3107AU IDNet+ card
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
IDNet Port Characteristics 7-2
Wiring to IDNet Devices
7-3
Troubleshooting IDNet Faults 7-7
Chapter 7
IDNet Wiring Rules
Introduction
In this Chapter

Table of Contents