E-5
The following lists the addressable devices approved for use with IDNet and
shows current rating and numbers allowed per loop.
Device Type Operating
Current mA
Maximum
Addressable
Point On
Analogue Loop
Maximum
Addressable
Points on
Analogue Line
4090-9116
IDNet Comms Isolator
0.5
(2 with LED on)
250 40*
4090-9118
Relay IAM with T-sense
0.5
(2 with LED on)
250 40*
4090-9117
Addressable Power
Isolator
0.5
(2 with LED on)
250 40*
4090-9119
Relay IAM with
unsupervised Input
0.5
(2 with LED on)
250 40*
409-9120
6 Point I/O
0.5 250 40*
4090-9001
Supervised IAM
0.65
(2.8 with LED
on)
250 40*
4090-9051
Supervised IAM
(encapsulated)
0.65
(2.8 with LED
on)
250 40*
4090-9101
Monitor ZAM
0.65
(2.8 with LED
on)
250 40*
4099-9032
4099-9701
4099-9702
Manual Call Point
0.65
(2.8 with LED
on)
250 40*
4090-9007
Signal IAM
1.0
(2.5 with LED
on)
125 40*
* Maximum allowed by AS 1670.1.
The maximum specified loop/line resistance is 40.
The maximum number of LEDs switched on by an IDNet in alarm is 20.
The 6 Point I/O LED is powered from the external 24V supply, not from the loop.
Note: The relays on the 6 Point I/O are not approved for switching field loads,
i.e. the contacts may only be used to switch loads within an earthed
cabinet.