3-3
The Basic TIC has the following LED indicators:
LED1. indicates communication loss with the CPU.
LED2. Indicates when an RUI ground fault search is active.
LED4. Indicates an RUI Style 7 primary trouble.
LED5. Indicates an RUI Style 7 secondary trouble.
{xe "transponder interface card (TIC): specifications"}
Table 4-1 lists the specifications for the TIC.
Table 3-1. TIC Specifications
Electrical Specifications
Input Voltage 18-33 VDC
Output Voltage 8 V @ 1 A; 100 mV p-p ripple
Input Current
87 mA, excluding the 8V load from legacy slave cards
powered by theTIC.
Environmental Specifications
Operating
Temperature
32 to 120 F (0 to 49 C)
Humidity
10% to 93% relative humidity at 90 F (32 C)