6-13
These switch and link settings should be used. These apply to T-GEN 50 software
version 1.7.
Table 6-6. T-GEN 50 Settings for NAC Operation
Alert to Evacuate
Change-Over Time
SW1
(T0)
SW2 (T1) SW3
(T2)
Setting on T-GEN 50
OFF OFF OFF 0 sec
ON OFF OFF 30 sec
OFF ON OFF 1 min
ON ON OFF 1.5 min
OFF OFF ON 3 min
ON OFF ON 5 min
OFF ON ON 10 min
ON ON ON Alert Only
SW1 to SW3 settings have no effect on Slave T-GEN 50s.
Table 6-7. T-GEN 50 Switch Settings for NAC Operation
SWITCH Name Setting on T-GEN 50
SW4 ALM I/P Supervision OFF (Supervision disabled)
SW5 ALM I/P OFF (Non-latching)
SW6 Evac Tone OFF
SW7 OFF for AS 2220 tone
ON for ISO 8201 + Keywords
SW8 Evac Message OFF for Evac Message 1 or Field
Recorded message,
ON for Evac Message 2 or Keywords
only in ISO 8201
Table 6-8. T-GEN 50 Link Settings for NAC Operation
Link Name Setting on T-GEN 50
1 BIAS Can be FITTED if PA or Background
Music not required
2 MASTER FITTED
3 REC EN Fit to record message.
4 TEST Fit for test tone during installation
5 SLAVE
N
OT FITTED
6 SLAVE / MASTER MASTE
R
7 FAULT=
DEF-/RELAY
RELAY
Using T-GEN 50 with 4100ES, Continued
T-GEN 50 Settings for
NAC Operation