Table 11. Meter readings
Circuit Type
Meter Reading
Class B (spur) Detector Circuit
From zone + to zone (each zone).
3.3k (EOLR).
From zone + to ground.
Open circuit.
From zone - to ground.
Open circuit.
Class B (spur) Notification Appliance Circuit (each signal circuit)
From + to ground.
Open circuit.
From - to ground.
Open circuit.
Resistance across circuit:
In one direction.
In the opposite direction.
10k (EOLR).
Low resistance (Load).
Class A (loop) Notification Appliance Circuit (each signal circuit)
From + to ground.
Open circuit.
From - to ground.
Open circuit.
From + OUT to + IN.
Less than 50.
From - OUT to IN.
Less than 50.
Resistance across circuit:
In one direction.
In opposite direction.
Open circuit.
Low resistance (Load).
Shielding
Shield to ground.
Open circuit.
Shield to -.
Open circuit.
Shield to +.
Open circuit.
MAPNET/IDNet Loops
From MX/IDNet/MAPNET + to ground.
Open circuit.
From MX/IDNet/MAPNET - to ground.
Open circuit.
Note:
Measuring from MAPNET/IDNet B+ to A+, or B- to A- reads as an open circuit due to the
channel isolators in the loop.
MX Loops
From MX+ one end to MX+ other end of the loop.
Less than 75.
From MX- one end to MX- other end of the loop.
Open circuit, loop isolators are
open.
From MX+ to MX- one end of the loop.
Open circuit.
From MX+ to MX- other end of the loop.
Open circuit.

Table of Contents

Other manuals for Simplex 4100ESi

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ESi and is the answer not in the manual?

Simplex 4100ESi Specifications

General IconGeneral
BrandSimplex
Model4100ESi
CategoryFire Alarms
LanguageEnglish

Related product manuals