Operation instructions
SIPOS 5 PROFITRON, HiMod
Page 36 Y070.020/GB
5 Commissioning
5
Commissioning
– For torque dependent cut-off mode
Hold down CLOSE
button (OPEN button for setting in
OPEN direction) for more than 2 s!
The actuator moves automatically until reaching the end
position. The actuator moves then shortly in the opposite
direction, to return to the end position again.
adapting cl.pos.
busy...
The display confi rms the correct setting.
If „increase it!“ or „decrease it“ is displayed, press the
ENTER button and adjust the slide wheel in the signaling
gear accordingly (refer to chapter 5.6.2) and repeat the
settings of end positions.
sign. gear ratio
adjustment ok!
12. Press ENTER button. The actuator changes to the „end-
pos. adjust“ parameter in the menu.
Now set the second end position of the mechanical positi-
on indicator, refer to chapter 5.6.5.
endpos. adjust
Now you can press the
button to get to the next parameter. If the Local/Remote button is pressed,
the actuator changes to the „Remote“ state. All changes confi rmed by ENTER are saved.
■
If the main menu was accessed from the „locPar“ state, and if the „Local/Remote“ button is
pressed, the actuator changes to the „Remote“ state and starts to move if a control command
from the DCS is present!
■
Once the end positions have been adjusted during commissioning, the central wheel must not
be moved! Otherwise a complete readjustment of the end positions is required.
5.6.4 Readjusting the end positions
Prerequisites
■
There must be a valid end position adjustment! If not, refer to the previous section „Initial setting“.
■
At the beginning of the end position adjustment, the valve must not be in a jammed state; if ne-
cessary, release it by means of the crank handle/hand wheel (see chapter 4.1).
■
Since the initial setting, the position of the central wheel must not be changed and will not be
changed during readjustment!
Readjustment can be canceled by pressing the and buttons at the same time. The actuator
is then ready for use with the original settings. Press the ENTER button, if the „check end-pos.!“,
message appears after canceling.
Operation sequence
1. Call up the main menu in the „locPar“ state, select „com-
missioning“ menu and enter code 9044.
close direction
clockwise
2. Press
button, until „endpos. adjust“ is indicated in the
display.
endpos. adjust
3. Press ENTER button.
In the display, the question appears whether completely
new positions have to be set.*
compl. new pos.?
Yes
4. Press button.
The display changes to „No“.
compl. new pos.?
No
___________________________
* The complete end position adjustment is described in the previous chapter.