Operation instructions
SIPOS 5 PROFITRON, HiMod
6
Parameters and possible parameter values
6 Parameters and possible parameter values
Parameter
Default value
Explanation
Parameter value Other param.
Err RemoteSource
keep position
A control wire interruption is detected for control:
- binary inputs with parameterization „NC“ (only for control via permanent or pulse contact),
- analog inputs with signal range 4 – 20 mA,
- eldbus control.
move to em. pos. When detecting an open-circuit behavior, the position programmed for the
emergency pos.“ parameter is automatically approached.
Display shows: emerg. Fault
keep position When an open circuit is detected, the current position is maintained.
Display shows: remote fault
keep proc value Actual process value is maintained.
The message is only display if the „Process controller“ software option is
active. Refer to Supplementary operation instructions „Process controller“
Y070.035.
moveTo FixSetPoi Fixed process value is approached and maintained
The message is only display if the „Process controller“ software option is
active. Refer to Supplementary operation instructions „Process controller“
Y070.035.
close tightly
Yes
Yes
Fig.: Close tightly
If the „close tightly“ function is active, closed-loop control within the end
position ranges is not possible.
If, within a end position range, the operation command in direction of this
end position is canceled or a STOP signal sent, the actuator continues
its operation until a torque-dependent cut-off occurs or a command in the
opposite direction is issued.
Even for „travel-dependent cut-off mode“ and for control via positioner or
process controller, similar to torque-dependent cut-off mode, the internal
operation command is extended until the end position (0 % or 100 %) is
reached.
No This setting is required, if closed-loop control is to be applied within the end
position ranges.
emergency pos.
0 %
0 % to 100 %
in 1% steps
When the emergency command is active or an open circuit is detected
and if the “open circ. beh”. parameter is set to “move to em. pos.”, the
position set is automatically approached.
inter.cont.CLOSE
torque-depen-
dent:
0% to 2%
travel-dependent
0% to 0%
From
[0 % to 0 %]
to
[0 % to 100 %]
in 1 % steps
With the „ inter.cont.CL“ parameter, a signal is sent to the process control, if
the actuator is within the programmed travel range.
The signal is active from 0 % to the programmed value.
inter.cont.OPEN
torque-depen-
dent:
98% to 100%
travel-dependent
100% to 100%
From
[0 % to 100 %]to
[100 % to 100 %]
in 1 % steps
With the „inter.cont. OPEN“ function, a signal is sent to the process control,
if the actuator is within the programmed travel range.
The output signal is active from the programmed value to 100 %.