2 Safety SMA Solar Technology AG
10 ClusterController-IA-en-10 Installation Manual
2.2 Qualifications of Skilled Persons
The work described in this document must only be performed by skilled persons. Skilled persons must
have the following qualifications:
• Training in the installation and commissioning of electrical devices
• Training in how to deal with the dangers and risks involved in installing and operating electrical
devices and plants
• Vocational training in the installation and configuration of IT systems
• Knowledge of how an inverter works and is operated
• Knowledge of all applicable standards and directives
• Knowledge of and compliance with this document and all the safety precautions
2.3 Safety Precautions
Electric Shock
If the enclosure of the Cluster Controller is not earthed, there is a danger of electric shock.
• Earth the enclosure of the Cluster Controller (for information on connecting the protective
conductor, see Section 6.13).
Damage to the Devices and Cables
Overvoltage (e.g. due to a flash of lightning) can cause damage to devices and cables.
• Ensure that the Cluster Controller is integrated in the existing overvoltage protection.
The Cluster Controller is not splashwater-protected (degree of protection: IP20). Consequently, it is
possible that moisture may penetrate the device.
• Only use the Cluster Controller in a dry, indoor environment.