7 Troubleshooting SMA Solar Technology AG
70 ClusterController-IA-en-10 Installation Manual
7.2 Faults in the Cluster Controller or the Connected Devices
Problem Cause and corrective measures
The Cluster Controller does not
start. The LEDs and the display are
off.
The Cluster Controller is not connected to the voltage supply.
Corrective measures:
Ensure that the three-pole plug for the voltage supply is
connected to terminal X1 of the Cluster Controller.
The voltage supply is reverse-connected or the top-hat rail
power supply unit is defective.
Corrective measures:
Ensure that the voltage supply is correctly connected
(see Section 6.13).
If the voltage supply is correctly connected, replace the
top-hat rail power supply unit.
The login page does not open and
the status LED ( ) flashes red.
The Cluster Controller could not start correctly. A system fault
has occurred.
Corrective measures:
Disconnect the Cluster Controller from the voltage
supply and reconnect to the voltage supply. Note that
this can lead to loss of plant data.
If the problem persists, contact the SMA Service Line
(see Section 11).

Table of Contents

Other manuals for SMA CLUSTER CONTROLLER

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMA CLUSTER CONTROLLER and is the answer not in the manual?

SMA CLUSTER CONTROLLER Specifications

General IconGeneral
Data LoggingYes
DisplayLCD
Power Supply24 V DC
Remote MonitoringYes
Protection ClassIP20
Communication InterfacesEthernet
Product TypeController
ManufacturerSMA

Related product manuals