Damage to the wall outlet
If the radio-controlled socket is operated in a wall outlet that is not suitable for the power of the
connected load, the wall outlet can become damaged.
• Only operate the radio-controlled socket in wall outlets that are suitable for the power of
the connected load.
2.3 Supported Products
Maximum Number of Devices
Maximum one SunnyHomeManager and one Plugwise Stretch per LAN (see
Section4.3, page32)
There may be a maximum of one SunnyHomeManager and one Plugwise Stretch in a
common local network (LAN). Otherwise communication disturbances may arise.
The SunnyHomeManager supports a maximum of 24 devices.
The term device includes all components that exchange data with the SunnyHomeManager, i.e.
SMA inverters, radio-controlled sockets, SunnySensorBox devices and smart appliances. The
Plugwise Stretch, the SMA Energy Meter, D0 meters and S0 meters are not included in this
definition as devices.
Of the 24 devices, a maximum of 12 devices may be actively controlled by the
SunnyHomeManager. Actively controlled means that the SunnyHomeManager not only
displays the consumption of the device, but actively switches the device. Even if the limit of a
maximum of 12devices is reached, further devices can be monitored via radio-controlled sockets
and visualized, so long as the maximum number of devices of 24 is not exceeded.
Example of a fully equipped energy management system:
A fully equipped energy management system (with a maximum of 24 devices) can consist of the
following components:
• 3 x SMA Inverters
• 1 x heat pump that is controlled by the SunnyHomeManager via a direct data connection.
• 20 x radio-controlled sockets
Due to the actively controlled heat pump, only 11 SMA radio-controlled socket can be
actively controlled by the SunnyHomeManager.
2 Safety
SMA Solar Technology AG
Installation ManualHoMan-IA-en-2012