Configuring the energy meters
1. If energy meters are connected to the SunnyHomeManager, select the energy meter type
connected to the respective meter input in the drop-down lists Meter input1, Meter input2
and Meter input3:
Connected energy meter type Drop-down list
Energy meter with D0interface
• Select D0.
Bidirectional meter with D0 interface
• Select D0.
• Activate the field Bidirectional meter
(Supply and feed-in).
☑ The area Meter input 2 is not
available.
Energy meter with S0interface
• Select S0.
• In the text field S0 pulses/kWh,
specify the pulse rate of the energy
meter (see energy meter
documentation).
SMA Energy Meter
• Select SMAEnergyMeter xxx. Here,
xxx is the placeholder for the
SMAEnergyMeter serial number. If
there are two SMAEnergyMeters in
the PV system, select the desired
SMAEnergyMeter.
• Activate the checkbox Bidirectional
meter (Supply and feed-in).
No energy meter
• Select no meter.
2. Select [Next].
☑ The page Extended PV System Properties opens.
Entering the PV System Data
1. Enter the system data.
2. Select [Next].
☑ The PV System Setup Assistant shows a summary of your entered data.
3. Select [Finish].
☑ SunnyPortal confirms successful registration of the SunnyHomeManager system in a
separate window.
4. To go to the SunnyHomeManager system, select [To the PV system].
☑ The SunnyHomeManager system opens.
5. Enter the system properties (see the user manual "SunnyHomeManager in SunnyPortal").