HRX-OM-Q026
Chapter 5 Display and Setting of Various Functions
5.9 Offset Function HRSH Series
5-26
Setting/Checking: Offset temperature
4. Press the [SEL] key once.
Setting screen of offset temperature appears on the digital display.
5. Set offset temperature with [▲] key or [▼] key, and press [SEL] key to enter.
Table 5.9-4 Offset temperature setting
Set value
Explanation
Default
Setting and checking are not available when offset
mode setting is OFF.
Centigrade
to
Offset temperature is set.
Setting temperature unit for Centigrade: 0.1
o
C
Setting temperature unit for Fahrenheit: 0.1
o
F
Fahrenheit
to
6. Press the [MENU] key once.
Returns to the main display (which shows the circulating fluid temperature).
PV
SV
PV
SV
This function adjusts the offset temperature in accordance with the
circulating fluid discharge temperature.
Circulating fluid temperature is controllable in the range of 5.0
o
C to
35.0
o
C (41.0
o
F to 95.0
o
F).
Note that when the circulating temperature is set to 5.0
o
C (41
o
F)
and the offset temperature is set to -20.0
o
C (-36.0
o
F), some of the
offset modes automatically adjust the offset temperature to 0.0
o
C
(0.0
o
F).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRSH Series and is the answer not in the manual?

SMC Networks HRSH Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRSH Series
CategoryChiller
LanguageEnglish

Related product manuals