EasyManuals Logo

SMC Networks HRSH200-A*-20 Series User Manual

SMC Networks HRSH200-A*-20 Series
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #103 background imageLoading...
Page #103 background image
HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
HRSH Series 5.18 Anti-snow coverage function
5-43
5.18 Anti-snow coverage function
5.18.1 Anti-snow coverage function
To prevent the snow coverage on the ventilation air outlet of the fan in
winter, this function operates fan automatically. If there is a possibility of the
snow coverage due to changes in the installation and operating environment
(season and weather), set this function in advance.
During the product operation
Repeats the fan operation with the maximum speed for 1 minute and the
normal controlled speed 29 minutes.
During the product stoppage
Repeats the fan operation with the maximum speed for 1 minute and
stoppage for 29 minutes.
The product operation can be operated by “RUN/STOP” key while the
anti-snow coverage function is ON.
z This function can be used while the power supply is ON.
z In extremely cold weather conditions, the heat generated by the
pump as described above may not be enough to prevent freezing.
z The automatic fan operation of the anti-snow coverage function
cannot be stopped with "RUN/STOP" key. To stop the automatic
operation of the fan, shut off the power or make this function “OFF”.
The power supply should be ON for this function. Otherwise this
function cannot start.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRSH200-A*-20 Series and is the answer not in the manual?

SMC Networks HRSH200-A*-20 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRSH200-A*-20 Series
CategoryChiller
LanguageEnglish

Related product manuals