HRX-OM-Q026-B
Chapter 3 Transport and Setting Up
HRSH Series 3.3 Installation
3-11
Power supply cable and Earth Leakage Breaker
Prepare the power supply shown in the following table. For the connection
between the product and power supply, use the power supply cable and
earth leakage breaker shown below.
Table 3-2 Power supply cable and Earth Leakage Breaker(Recommended)
Earth leakage breaker
*1
Model
Power
supply
voltage
Terminal
block
screw
diameter
Recomm
ended
crimp
terminal
Cable qty. x
size
Rated
current
[A]
Sensitivity
of leak
current
[mA]
HRSH150-A∗-20-∗
30
HRSH200-A∗-20-∗
40
HRSH250-A∗-20-∗
AC200/
200-230V
50/60Hz
3phase
M5 R8-5
4 cores x
AWG8
(4 cores x
8mm2)
(including
ground)
50
30
R5.5-5
3x5.5mm2
(3xAWG10)
HRSH250-A∗-40-∗
AC380-415V
50/60Hz
3phase
M5
R14-5
For
ground
line
1x14mm2
(1xAWG6)
For
ground line
30 30
*1: A specified earth leakage breaker is installed for option B [Earth leakage breaker] of each model.
If the product is not option B [Earth leakage breaker], please prepare an earth leakage breaker by
the customer side.
A specified earth leakage breaker is installed for HRSH250-A∗-40-∗ .
3.3.3 Preparation and wiring of power supply cable
z The electrical facilities should be installed and wired in
accordance with local laws and regulations of each country and by
a person who has knowledge and experience.
z Check the power supply. Operation with voltages, capacities and
frequencies other than the specified values can cause fire and
electrical shock.
z Wire with an applicable cable size and terminal. Forcibly mounting
with an unsuitable size cable ma