HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
HRSH Series 5.20 Alarm customizing function
5-47
Table 5.20-2 Alarm setting and customizing (2/4)
①Alarm operations ②Alarm threshold and others∗4
Code Alarm name
Display
A.STP
A.RUN
P.RUN
OFF
Display
Default
setting
Settable range
Set temperature
1.0℃
(33.8 ゚ F)
(----)
∗5
1.0~34.0℃
(33.8~93.2 ゚ F)
Monitoring method
0
0~3
Monitoring start timer
----(0)∗6
0 to 600 minutes
Range over detection timer
AL04
Circulating fluid
discharge temp.
drop
● ○ - ●
5 5 to 999
seconds
AL05
High circulating
return temp.
- ○ --- - -
Set pressure
AL08
Circulating fluid
discharge
pressure rise
○ ● - ●
1.00MPa
(145PSI)
(----)
∗7
0.05 to 1.00MPa
(7~145PSI)
Set pressure
AL09
Circulating fluid
discharge
pressure drop
○ ● - ●
0.05MPa
(7PSI)
(----)
∗8
0.05 to 1.00MPa
(7 to 145PSI)
AL10
High compressor
suction temp.
● - ○ -- -
AL11
Low compressor
suction temp.
● - ○ -- -
AL12
Low super heat
temperature
● - ○ -- -
AL13
High compressor
discharge
pressure
● - ○ -- -
AL15
Refrigerant circuit
pressure (high
pressure side)
drop
● - ○ -- -
AL16
Refrigerant circuit
pressure (low
pressure side)
rise
● - ○ -- -
∗4: Values in ゚ F are displayed when SE12 is F, and PSI are displayed when SE13 is PSI.
∗5: The default setting when AS05 is OFF.
∗6: The default setting when AS21 is 2 or 3.
∗7: The default setting when AS07 is OFF.
∗8: The default setting when AS09 is OFF.