Chapter 2 Name and Function of Parts
2.4 Operation display panel HRSH Series
2-4
2.4 Operation display panel
The operation panel on the front of the product controls the basic operation
of the product.
Fig. 2-3 Operation display panel
Table 2-3 Operation display panel
No Description Function
Reference
page
PV
Displays the temperature and pressure of the circulating
fluid and alarm codes.
Digital display
(7 segment,
4 digits)
SV
Displays the set temperature of the circulating fluid and
the set values of other menus.
5.2
[
o
C
o
F ] lamp Displays the unit of display temperature (
o
C or
o
F). 5.12
[MPa PSI] lamp Displays the unit of display pressure (MPa or PSI). 5.13
[REMOTE] lamp Lights up during remote operation by communication. 5.21
[RUN] lamp
Lights up when the product is started and in operation. Goes off
when the product is stopped.
Blinks during stand-by for stop (Interval 0.5 seconds).
Blinks during independent operation of the pump (Interval 0.3
seconds).
Blinks during anti-freezing function (At standby: Interval 2
seconds, At operation: Interval 0.3 seconds).
Blinks during warming up function (At standby: lit on for 0.5
seconds and off for 3 seconds, At operation: interval 0.3
seconds.)
4.4
Flashes with buzzer when alarm occurs (Interval 0.3 seconds). 5.3
[ALARM] lamp
Blinks while AL25 is OFF (lit on for 0.5 seconds and off 3
seconds.)
5.20
[ ] lamp Lights up when the fluid level lowers. 4.3
[ ] lamp Lights up while the run timer or stop timer function is working. 5.6
[ ] lamp
Lights up when the product is in automatic operation.
5.9
[RUN/STOP] key
Makes the product start or stop.
4.4
[MENU] key
Shifts the main menu (display screen of temperature) the other
menu (entry of set values and monitor screen).
[SEL] key
Changes the item in menu and enters the set value.
5.1
[] key
Decreases the set value.
[] key
Increases the set value.
-
[PUMP] key
When the [MENU] and [RUN/STOP] keys are held down
simultaneously, the pump starts running independently.
4.3
Press the [] and [] keys simultaneously. This will stop the alarm
buzzer and reset the [ALARM] lamp.
[RESET] key
Keep the [] and [] keys pressed down simultaneously for 3
seconds to reset AL46 and AL48.(After resetting AL48,
WAIT(
) will be displayed and the product cannot run for 40
seconds. Restart 40 seconds later after resetting.
6.3