HRX-OM-Q026-B
Chapter 3 Transport and Setting Up
HRSH Series 3.3 Installation
3-15
3.3.4 Contact input/output communicatin wiring
The product has contact input/output communication that has the functions
that described below. Wire referring to each function’s chapter. (For the
details of the functions, refer to the operation manual communication
function.)
z Run/stop inputRemote signal input (Refer to 3.3.5 Wiring of
Run/stop inputRemote signal input.)
z External switch signal input (Refer to 3.3.6 Wiring of external
switch signal input.)
z Output of contact output signal (Refer to 3.3.7 Wiring of contact
output signal.)
Use the signal cable described below for wiring of each function.
Signal cable
Use the cable and terminals as follows below for wiring of each function.
Table 3-3 Signal cable
Terminal specification
Terminal block
screw diameter
Crimp terminal
Cable specification
M3
1.25Y3
0.75 mm
2
(AWG18)
Shielded cable
3.3.5 Wiring of Run/stop signal inputRemote signal input
Run/stop signal inputRemote signal input enable the product to be run and
stopped or switched DIO REMOTE and DIO LOCAL remotely by applying a
contact signal input. This chapter explains examples of wiring.
Select DIO mode as the communication mode to activate the Run/stop
signal inputremote signal input after wiring referring to the operation
manual communications function.
Tips
This product has two input signals. These can be customized depending on
the customer’s application.
The capacity of the output contact of the product is limited. If the capacity is not
large enough, install a relay, etc. (to allow for larger capacity). At the same time,
ensure the input current of the relay is small enough in relation to the contact
ca
p
acit
y
of the
p
roduct.
Be sure to lock out and tag out the breaker of the facility power supply
(customer power supply facility) before wiring.