HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
HRSH Series 5.21 Communication function
5-67
5.21 Communication function
5.21.1 Communication function
The product can have contact input/output and serial communication.
Refer to the Operation Manual for communication for details.
5.21.2 Communication function setting and checking
The table below explains the setting items of the communication function
and the initial values.
Table 5.21-1 List of set communication function
Display Item Contents Default setting
Communication mode Sets communication mode.
LOC
Serial protocol
Sets serial communication protocol.
MDBS
Communication specification Sets standard of the serial communication.
485
RS-485 terminal
Sets of the terminal of RS-485.
OFF
   
   
   
   
 
Slave address
Sets slave address.
1 (----)1
Mod
bus
Communication
speed
Sets communication speed.
19.2 (----)1
Slave address
Sets slave address.
---- (1)1
Communication
speed
Sets communication speed.
---- (9.6)1
BCC
Sets error detection code.
---- (ON)1
Data length
Sets data length.
---- (8BIT)1
Parity check
Sets parity check.
---- (NON)1
Stop bit length
Sets stop bit length
---- (2BIT)1
Response delay time
Sets time to delay the response message.
---- (0)1
Serial communication
Simple communication
protocol
Communication range
Sets communication range.
---- (RW)1
Contact input signal 1 Sets contact input signal 1. RUN
Contact input signal 1 type
Sets input type of contact input signal 1.
ALT
Contact input signal 1 Delay
timer (time delay) of reading
Sets the delay timer of reading of contact
input signal 1.
---- (0)2
Contact input signal 1 OFF
detection timer
Sets the contact input signal 1 OFF
detection timer
---- (0)2
Contact input signal 2
Sets contact input signal 2.
OFF
Contact input signal 2 type
Sets input type of contact input signal 2.
ALT
Contact input signal 2 Delay
timer (time delay) of reading
Sets the delay timer of reading of contact
input signal 2.
---- (0)3
Contact input signal 2 OFF
detection timer
Sets the contact input signal 2 OFF
detection timer
---- (0)3
Contact output signal 1
function
Sets contact output signal 1.
RUN
Contact output signal 1
operation
Sets input type of contact output signal 1.
A
Contact output signal 1
selected alarm
Sets alarm which is selected for contact
output 1.
---- (AL.01)4
Contact output signal 2
function
Sets output signal function of contact output
2.
RMT
Contact output signal 2
operation
Sets output signal operation of contact
output 2.
A
Contact output signal 2
selected alarm
Sets alarm which is selected for contact
output 2.
---- (AL.01)5
Contact output signal 3
function
Sets output signal function of contact output
3.
ALM
Contact output signal 3
operation
Sets output signal operation of contact
output 3.
B
Contact input/output communication
Contact output signal 3
selected alarm
Sets alarm which is selected for contact
output 3.
---- (AL.01)6
1: The default setting when CO02 is PRO1 or PRO2. 4: The default setting when CO23 is A.SEL.
2: The default setting when CO15 is SW-A or SW-B. 5: The default setting when CO26 is A.SEL.
3: The default setting when CO19 is SW-A or SW-B. 6: The default setting when CO29 is A.SEL.