HRX-OM-Q026-B
Chapter 3 Transport and Setting Up
3.4 Piping HRSH Series
3-24
3.4 Piping
Piping port size
Table 3-10 Piping port size
Name Port size
1
Recommended
tightening torque
Recommended piping
specification
Circulating fluid supply Rc1
36 to 38N・m
1.0MPa and more
Circulating fluid return Rc1
36 to 38N・m
1.0MPa and more
Automatic fluid-fill port Rc3/8
28 to 30N・m
1.0MPa and more
(Automatic fluid -fill pressure
0.2 to 0.5MPa)
Overflow port Rc1
36 to 38N・m
ID25mm and more
Length 5m and less
Tank drain port Rc3/4
28 to 30N・m
ID 19mm and more
【Tips】
<In case of HRSH∗∗∗-∗N-∗>
A set of thread adapters that converts the connections from Rc to NPT is
enclosed as an accessory. Be sure to use this for NPT piping.
<In case of HRSH∗∗∗-∗F-∗>
A set of thread adapters that converts the connections from Rc to G is
enclosed as an accessory. Be sure to use this for G piping.
z Connect piping firmly. Incorrect piping might cause leakage of
supplied or drained leakage and wet surrounding area and facility.
z Pay attention not to allow dust and foreign materials to enter into
water circuit etc. during connection of piping.
z Hold the piping port firmly with specific wrench when tightening.
z The piping should be selected with due consideraton of pressure
and temperature. Otherwise the piping can burst in service.