Chapter 5 Display and setting of various functions
5.20 Alarm customizing function HRSH Series
5-52
Table 5.20-7 List of set alarm customizing function(3/3)
Object alarm
Display Content
Code Alarm name
Change content
Initial
setting
Changing of circulating
fluid outlet pressure
sensor failure
AL25
Circulating fluid
discharge pressure
sensor failure
Alarm operation A.STP
Changing of pump
maintenance
AL28
Pump maintenance
Alarm operation OFF
Changing of fan
maintenance
AL29 Fan maintenance Alarm operation OFF
Changing of
compressor
maintenance
AL30
Compressor
maintenance
Alarm operation OFF
Changing of dust-proof
filter maintenance
AL40
Dust-proof filter
maintenance
Alarm operation A.RUN
Changing of power
stoppage alarm
AL41
Power stoppage
Alarm operation A.STP
1. Press and hold the [MENU] key for approx. 2 sec.
Repeat pressing the key until the setting screen for alarm buzzer sound [
]
appears on the digital display.
PV
SV
PV
SV
PV
SV
PV
SV
Low tank level Setting and checking
2. Press the [SEL] key once.
The set screen of changing of low tank level is displayed on the digital display.
PV
SV
3. Select changing of low tank level from the table below with [] key or [] key, and
confirm by pressing “SEL”.
Table 5.20-8 List of set value
Set value Explanation
Initial value
(Default setting)
Operation continues when this alarm signal is
generated.
Operation is stopped when this alarm signal is
generated.
[MENU]
Press and
hold
[MENU]
Press and
hold
[MENU]
Press and
hold