Chapter 6 Alarm indication and trouble shooting
HRSH Series 6.3 Troubleshooting
6-7
Table 6-3 Alarm code list and Troubleshooting (3/3)
Code Alarm name
Alarm
operation*1
(Default
setting)
Cause / Remedy
(Press the reset key after eliminating the
cause.)
AL43 Fan breaker trip P.RUN
Release the fan breaker
trip referring to [6.3.2
How to release the fan
breaker trip].
AL44 Fan inverter error P.RUN
AL45 1
Compressor breaker
trip
P.RUN
AL46
Compressor inverter
error
P.RUN
AL47 1
Pump breaker trip A.STP
AL48 Pump inverter error A.STP
Check that there is
no power failure
such as ground
fault, short circuit,
voltage fluctuation,
abnormal
interphase voltage,
open phase, surge.
Keep the [] and [] keys
of the operation display
panel pressed down
simultaneously for 10
seconds to reset. After
resetting AL48,
WAIT(
) will be
displayed and the product
cannot run for 40 seconds.
Restart 40 seconds later
after resetting.
*1 This alarm does not occur on the product of power specification ‘-20’.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRSH200-A*-20 Series and is the answer not in the manual?

SMC Networks HRSH200-A*-20 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRSH200-A*-20 Series
CategoryChiller
LanguageEnglish

Related product manuals