Chapter 5 Display and setting of various functions
5.4 Inspection monitor menu HRSH Series
5-12
Check of the accumulated operation time of the compressor
9. Press the [SEL] key once.
The accumulated operation time of the compressor is displayed on the digital display.
PV
SV
Displays the accumulated operation time of the compressor. Refer to Table 5.4-2 for
the display.
AL30 Compressor maintenance alarm is generated when the accumulated operation
time of the compressor reaches 30,000 hours (
) or more. For details, refer to
Chapter 6 Alarm indication and trouble shooting.
Check of the accumulated operation time
10. Press the [SEL] key once.
The accumulated operation time is displayed on the digital display.
PV
SV
Displays the accumulated operation time. Refer to Table 5.4-2 for the display.
Check of the accumulated operation time
11. Press the [SEL] key once.
The accumulated operation time of the dust-proof filter is displayed on the digital
display.
PV
SV
Displays the accumulated operation time of the dust-proof filter. Refer to Table 5.4-2
for the display.
AL40 dust-proof filter maintenance alarm is generated when the accumulated
operation time of the compressor reaches 500 hours (
) or more. For details,
refer to Chapter 6 Alarm indication and trouble shooting.