EasyManuals Logo

SMC Networks HRSH200-A*-20 Series User Manual

SMC Networks HRSH200-A*-20 Series
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
5.6 Run timer, stop timer function HRSH Series
5-18
Stop timer Setting and checking
4. Press the [SEL] key once.
The set screen of stop timer is displayed on the digital display.
PV
SV
5. Set stop timer as the table below with [] key or [] key, and confirm by pressing “SEL”.
Table 5.6-3 List of set value
Set value Explanation
Initial value
(Default setting)
Timer OFF
to
Operation stops after set time.
Setting unit is 0.5 hour
E.g. Set at 4:30pm. Operation stops 1 hour and 30 minutes later (at 6:00pm).
PV
SV
6. Press the [MENU] key once.
Return to the screen displaying the circulating fluid temperature.
PV
SV
7. Once the run timer is set leave the power supply to the product on. The product will start
automatically in the set time.
When the stop timer is set, leave the product running. The product will stop automatically
in the set time.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRSH200-A*-20 Series and is the answer not in the manual?

SMC Networks HRSH200-A*-20 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRSH200-A*-20 Series
CategoryChiller
LanguageEnglish

Related product manuals