HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
0 HRSH Series
5-36
7. Select from the table below with [] key or [] key, and confirm by pressing
“SEL”. Select
, then the accumulated operating time of the compressor is
reset. The display returns to the main menu.
Table 5.15-4 List of set value
Set value Explanation
Initial value
(Default setting)
Not reset
Compressor accumulated operating time is
reset
Dust-proof filter accumulated operating time reset
8. Press the [SEL] key once.
The set screen of dust-proof filter accumulated operating time reset is displayed on the
digital display.
PV
SV
9. Select from the table below with [] key or [] key, and confirm by pressing
“SEL”. Select
, then the accumulated operating time of the dust-proof filter is
reset. The display returns to the main menu.
Table 5.15-5 List of set value
Set value Explanation
Initial value
(Default setting)
Not reset
Dust-proof filter accumulated operating time is
reset
10. Press the [MENU] key once.
Return to the main screen (screen displaying the circulating fluid temperature).
PV
SV