To connect ACand ground:
WARNING!
Turn OFF the AC before connecting the AC terminals.
1. TurnOFFtheACcircuitbreaker.
2.
OpentheConnectionUnitcover:ReleasethesixAllenscrewsandcarefullymovethecover
horizontallybeforeloweringit.
CAUTION!
When removing the cover, make sure not to damage internal components. SolarEdge will not be
held responsible for any components damaged as a result of incautious cover removal.
3. Removetheterminalblockcover.
4.
InsertthecablethroughtheACdrillguidethatwasopened.
NOTE
Connect the equipment grounding before connecting the AC wires to the AC terminal block.
Veillez à relier le conducteur de PE (la terre) avant de connecter les fils CA au bornier CA.
5. Connectthegroundingwiretothegroundingterminalblockandtightenwithatorqueof
15N*m/12lb*ft.
6.
RemovethescrewsfromtheACterminalblocks.
NOTE
Apply heat shrink insulation to the lug barrels.
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4
38
Connecting the AC Grid and Grounding to the Connection Unit