Appendix C: External Fan Maintenance and
Replacement
ThePrimaryandSecondaryUnitshavetwofanseach:oneisinternalandtheotherisaccessiblefromthe
outsideoftheunit.Thisappendixdescribesexternalfanreplacement.
AfanreplacementkitisavailablefromSolarEdge.
Figure 50: Primary Unit (left) and Secondary Unit (right) external fans
Fan Maintenance
Atleastonceayear,openthefanscreenandcleantheaccumulateddustusingabrush.
IftheSetAppStatusscreendisplaysthestatusNot Workingforthefan(refertoMainInverterStatuson
page47),replacethefanasdescribedinthenextsection.
External Fan Replacement
1. TurnOFFtheinverterON/OFF/Pswitch,andwaituntilthegreenLEDisblinking,indicatingthatthe
DCvoltageissafe(<50V),orwaitfiveminutesbeforecontinuingtothenextstep.
2. DisconnecttheACtotheinverterbyturningOFFthecircuitbreakersonthedistributionpanel.
3.
Useastandardscrewdrivertounfastenthetwoscrewsofthefancoverandopenthefandoor.
4.
Disconnectthefanconnectorandremovethefan.
5. Connectthefanconnectortothenewfan.
6. Closethefandoorandfastenthecoverscrews.