SE66.6KUS SE100KUS SE43.2KUS Units
OUTPUT
Rated AC power output 66600 100000 43200 VA
Maximum AC power output 66600 100000 43200 VA
AC Output Line Connections 4-wire WYE (l1-L2-L3) plus PE
4-wire WYE (l1-L2-
L3) plus PE or 3 wire
Delta
AC output voltage minimum-
nominal-maximum (L-N)
1
244-277-305 105-120-132.5 Vac
AC output voltage minimum-
nominal-maximum (L-L)
1
422.5-480-529 182-208-229 Vac
AC frequency min-nom-max
1
59.3-60-60.5 59.3-60-60.5 Hz
Max. continuous output current
(per Phase)@277V
80 120 A
GFDI threshold 1 A
Utility monitoring, islanding
protection ,
Configurable Power Factor,
country configurable Thresholds
Yes
INPUT
Maximum DC power (Module
STC)
90000 /45000 135000/45000 58200/19400 W
Transformer-less, ungrounded Yes
Maximum input voltage DC to
Gnd
500 300 Vdc
Maximum input voltage DC+ to
DC-
1000 600 Vdc
Nominal input voltage DC to Gnd 425 200 Vdc
Nominal input voltage DC+ to
DC-
850 400 Vdc
Maximum input current 80 120 114 Adc
Maximum input short circuit
current
120 135 Adc
Reverse-polarity protection Yes
1