SolarEdge SE66.6KUS - Default Trip Limits and Times According to IEEE1547

SolarEdge SE66.6KUS
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RecommendedOCPDsizepergrid:
Inverter 480 VAC 208 VAC
SE66.6KUS 184A ---
SE100KUS 277A ---
SE43.2KUS --- 277A
Inverter
Inom [A]
Peak
[A]
1 cycle
RMS[A]
3 cycle
RMS[A]
Duration
(ms)
SE43.2-US 120 210 75 49.5 54
SE66.6K-
US
50 118 40 24 30
SE100K-
US
120 210 75 49.5 54
Duration-timebywhichfaultcurrentreaches0
1cycleRMS-theintegralononecycle(60Hz)duration
3cycleRMS-theintegralon3-cycleduration
Default Trip Limits and Times According to
IEEE1547
NOTE
The inverters are equipped with adjustable utility protective function set-points, and can be aggregated
above 30kW on a single Point of Common Connection. The default settings are in compliance with
IEEE1547. Utility authorization is required to change these set-points.
Voltage Range (% of Base Voltage) Max. Clearing Time (Sec)
V < 50% 0.16
50 % < V < 88% 2.00
110% < V < 120 1.00
V > 120 % 0.16
Frequency Range (Hz) Max. Clearing Time (Sec)
> 60.5 0.16
< 59.3 (Hawaii 57) 0.16
Three Phase Inverter with Synergy Technology - Technical Specifications (North America)
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4