RecommendedOCPDsizepergrid:
Inverter 480 VAC 208 VAC
SE66.6KUS 184A ---
SE100KUS 277A ---
SE43.2KUS --- 277A
Inverter
Inom [A]
Peak
[A]
1 cycle
RMS[A]
3 cycle
RMS[A]
Duration
(ms)
SE43.2-US 120 210 75 49.5 54
SE66.6K-
US
50 118 40 24 30
SE100K-
US
120 210 75 49.5 54
Duration-timebywhichfaultcurrentreaches0
1cycleRMS-theintegralononecycle(60Hz)duration
3cycleRMS-theintegralon3-cycleduration
Default Trip Limits and Times According to
IEEE1547
NOTE
The inverters are equipped with adjustable utility protective function set-points, and can be aggregated
above 30kW on a single Point of Common Connection. The default settings are in compliance with
IEEE1547. Utility authorization is required to change these set-points.
Voltage Range (% of Base Voltage) Max. Clearing Time (Sec)
V < 50% 0.16
50 % < V < 88% 2.00
110% < V < 120 1.00
V > 120 % 0.16
Frequency Range (Hz) Max. Clearing Time (Sec)
> 60.5 0.16
< 59.3 (Hawaii – 57) 0.16
Three Phase Inverter with Synergy Technology - Technical Specifications (North America)
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4
85