EasyManua.ls Logo

SolarEdge SE66.6KUS - Ethernet Connection

SolarEdge SE66.6KUS
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection Unit Communication Board
OpentheConnectionUnitcovertoaccessthecommunicationboardto:
l connectastandardRJ45connectorforEthernet.
l connectRS485wirestotheterminalblocksforRS485connection.Therearetwo3-pinterminal
blocks,oneforconnectingtheprecedingdeviceinthebusandoneforconnectingthefollowing
device.Additionally,theRS485porthasabuilt-insurgeprotection.
Figure 36: Connection Unit Communication board
Removing the Connection Unit Cover
IftheConnectionUnitisnotalreadyremoved,removeitasdescribedinthefollowingsection.
To remove the Connection Unit cover:
1. TurnOFFtheinverterON/OFFswitch,andwaituntilthegreenLEDisblinking,indicatingthattheDC
voltageissafe(<50V),orwaitfiveminutesbeforecontinuingtothenextstep.
2. DisconnecttheACtotheinverterbyturningOFFthecircuitbreakersonthedistributionpanel.
3.
OpentheConnectionUnitcover:
a.ReleasethesixAllenscrewsofthecover.
b.Tiltthetopofthecovertowardsyou.
c.Slidethecoverdownandremoveit.
CAUTION!
When removing the cover, make sure not to damage internal components. SolarEdge will not be
held responsible for any components damaged as a result of incautious cover removal.
Lors du retrait du couvercle, assurez-vous de ne pas endommager les composants internes.
SolarEdge ne peut être tenue pour responsable des composants endommagés à la suite d'une
imprudence dans le retrait du couvercle.
Creating an Ethernet (LAN) Connection
ThiscommunicationoptionenablesusinganEthernetconnectiontoconnecttheinvertertothe
monitoringplatformthroughaLAN.
Ethernetcablespecifications:
l Cabletype–ashieldedEthernetcable(Cat5/5ESTP)maybeused
l Maximumdistancebetweentheinverterandtherouter–100m/330ft.
Chapter 6: Setting Up Communication
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4