7.
CrimpthelugsontheACwires.
CAUTION!
Onlyusecompressionlugsoftheone-holestandardbarrel600vtype.Donotuse
mechanicallugs(chairlugs)astheymayposeasafetyrisk.
NOTE
ThefollowingaretherequirementsfortheLugs:
l Boltholesize:M*(5/16").
l Compressionlugsonly(nomechanicallugs).
l Compressionlugsoftheone-hole,standardbarrel,600vtype.
l 4/0lugsshallbeofthenarrowtonguetype
l Maximumwiresize:4/0AWG
l Maximumlugtonguethickness:0.16"
l Maximumlugtonguewidth:0.9"
8. Applyheatshrinkinsulationtothelugbarrels.
9. Connectthewirestotheterminalblockswithapropertoolaccordingtothelabelsontheterminals.
10. Tightenthescrewsofeachterminalwithatorqueof15.0N*m
Wire type Connect to terminal
Line 1 L1
Figure 30: Wire connections to terminal block
Line 2 L2
Line 3 L3
Neutral N
11. Placethecoverontheterminalblockandpushuntilyouhearaclick.
Connecting the Strings to the Connection Unit
YoucanconnectsystemswithmultipleDCstringsinparalleltotheDCinputterminalsoftheConnection
Unit.
NOTE
The DC bus of each unit is separate and not shared for all units. Therefore in addition to following the
inverter design rules, each unit should follow the unit design rules as detailed in Technical
Specifications.
Chapter 4: Connecting the AC and DC Strings to the Connection Unit
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4
39