Three Phase Inverters for the
277/480V Grid
Three Phase
Inverters for the
208V Grid
SE66.6KUS SE100KUS SE43.2KUS Units
Ground-fault isolation detection 350 MΩ Sensitivity per Unit
CEC weighted efficiency 98.5 97 %
Night-time power consumption < 12 W
ADDITIONAL FEATURES
Supported communication
interfaces
RS485, Ethernet, Cellular GSM (optional)
Rapid Shutdown
NEC2014 and NEC201 7 compliant/certified, upon AC Grid
Disconnect
RS485 Surge Protection Built-in
DC Safety Unit
DC Disconnect 1000V /2 x 40A 1000V/3 x 40A
1
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, UL1998, CSA 2.22
Grid connection standards IEEE 1547, Rule 21, Rule 14 (HI)
Emissions FCC part 15 class A
INSTALLATION SPECIFICATIONS
Number of units 2 3
AC output conduit size / AWG
range / Max PE AWG
1.5"/2/0/6 2"/4/0/4
2
DC input conduit size /Terminal
Block AWG Range'Number fo
Strings
2 X 1.25" /6-14 /6
strings
2 X 1.25" /6-14 /9 strings
Dimensions (HxWxD)
Primary Unit:37 x 12.5 x 10.5 / 940 x 315 x 260
Secondary Unit:21 x 12.5 x 10.5 / 540 x 315 x 260
in / mm
Weight Primary Unit:105.8/48 Secondary Unit:99.2 /45 Ib / kg
Operating temperature range
3
-40ºF to+140/ 40ºC+60 ºF / ºC
Cooling Fans (user replaceable)
Noise < 60 dBA
Protection rating NEMA 3R
Braket Mounted (Brackets
Provided)
1
Pending
2
Single input option per unit (up to 3AWG) available
3
For power de -rating information refer to https://www.solaredge.com/sites/default/files/se-temperature-derating-
note-na.pdf
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4