EasyManua.ls Logo

SolarEdge SE66.6KUS - Page 85

SolarEdge SE66.6KUS
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Three Phase Inverters for the
277/480V Grid
Three Phase
Inverters for the
208V Grid
SE66.6KUS SE100KUS SE43.2KUS Units
Ground-fault isolation detection 350 MΩ Sensitivity per Unit
CEC weighted efficiency 98.5 97 %
Night-time power consumption < 12 W
ADDITIONAL FEATURES
Supported communication
interfaces
RS485, Ethernet, Cellular GSM (optional)
Rapid Shutdown
NEC2014 and NEC201 7 compliant/certified, upon AC Grid
Disconnect
RS485 Surge Protection Built-in
DC Safety Unit
DC Disconnect 1000V /2 x 40A 1000V/3 x 40A
1
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, UL1998, CSA 2.22
Grid connection standards IEEE 1547, Rule 21, Rule 14 (HI)
Emissions FCC part 15 class A
INSTALLATION SPECIFICATIONS
Number of units 2 3
AC output conduit size / AWG
range / Max PE AWG
1.5"/2/0/6 2"/4/0/4
2
DC input conduit size /Terminal
Block AWG Range'Number fo
Strings
2 X 1.25" /6-14 /6
strings
2 X 1.25" /6-14 /9 strings
Dimensions (HxWxD)
Primary Unit:37 x 12.5 x 10.5 / 940 x 315 x 260
Secondary Unit:21 x 12.5 x 10.5 / 540 x 315 x 260
in / mm
Weight Primary Unit:105.8/48 Secondary Unit:99.2 /45 Ib / kg
Operating temperature range
3
-40ºF to+140/ 40ºC+60 ºF / ºC
Cooling Fans (user replaceable)
Noise < 60 dBA
Protection rating NEMA 3R
Braket Mounted (Brackets
Provided)
1
Pending
2
Single input option per unit (up to 3AWG) available
3
For power de -rating information refer to https://www.solaredge.com/sites/default/files/se-temperature-derating-
note-na.pdf
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4
84
Three Phase Inverter with Synergy Technology - Technical Specifications (North

Table of Contents

Related product manuals