CosPhi
1.00
Limit
No Limit
Country
USA2
Voltage
850 Vdc
Temp
156 F
Fan
OK
Switch Off. Production disabled ›
Commissioning›
l Inverter:Theinverterserialnumber
l Power:TheACoutputpower
l Voltage (Vac):TheACoutputvoltage
l Frequency:TheACoutputfrequency
l P_OK: xxx of yyy: Thereisaconnectiontothepoweroptimisersandatleastonepoweroptimiseris
sendingmonitoringdata.XXXisthenumberofpoweroptimisersforwhichtelemetrieshavebeen
receivedinthelasttwohours.YYYisthenumberofpairedpoweroptimisersidentifiedduringthe
mostrecentpairingprocess.IfXXXandYYYarenotequal,theremaybeaprobleminoneormore
poweroptimisers.
l S_OK:Theconnectiontothemonitoringplatform.(Server Connectedappearsonlyiftheinverteris
connectedtothemonitoringplatform).
l Status: Theinverteroperationstatus:Off,NotPaired,NightMode,Error,Pairing,orProduction
l Switch:IndicatesthepositionoftheinverterON/OFF/Pswitch:On,Off,orPposition.
l CosPhi:Indicatestheratiobetweenactiveandreactivepower.Anegativevalueindicatesalagging
CosPhi.
Formoreinformation,refertothePowerControlApplicationNote,availableonthe
SolarEdgewebsiteathttps://www.solaredge.com/sites/default/files/application_
note_power_control_configuration.pdf.
l Limit:Theinvertermaximumoutputpower
l Country:Theselectedcountryandgridsetting
l Voltage (Vdc):TheDCinputvoltage
l Temp(°Cor°F):Theinverterheatsinktemperature
l Fan:Providesinformationaboutthefanstatus:OK,orNotworking.Formoreinformation,referto
ExternalFanMaintenanceandReplacementonpage76.
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4
48
Main Inverter Status