130
Technical Data
Model
X3-Hybrid-
5.0-D
X3-Hybrid-
6.0-D
X3-Hybrid-
8.0-D
X3-Hybrid-
10.0-D
X3-Hybrid-
10.0K-D
X3-Hybrid-
12.0-D
X3-Hybrid-
12.0K-D
X3-Hybrid-
15.0-D
X3-Hybrid-
5.5-D LV
X3-Hybrid-
8.3-D LV
Current
(inrush)(at 50
µs) [a.c. A]
30
Rated output
current [a.c. A]
7.2 8.7 11.6 14.5 17.5 21.8 14.5 21.8
Power factor
range
1 (0.8 leading ... 0.8 leading)
Total
harmonic
distortion
(THDi)
< 3%
Maximum
output fault
current (at
5ms) [a.c. A]
68
Maximum
output
overcurrent
protection
[a.c. A]
68
Rated AC
input power
[W]
10000 12000 16000 20000 20000 20000 11000 12100
Max. AC input
apparent
power [W]
10000 12000 16000 20000 22000 22000 11000 12100
Nominal AC
voltage [a.c. V]
415/240; 400/230; 380/220 127
Nominal AC
frequency
[Hz]
50/60 50/60
Max. AC
current
[a.c. A]
16.1 19.3 25.8 32.0 32.0 32.0 32.0 32.0
• Battery
Model
X3-Hybrid-
5.0-D
X3-Hybrid-
6.0-D
X3-Hybrid-
8.0-D
X3-Hybrid-
10.0-D
X3-Hybrid-
10.0K-D
X3-Hybrid-
12.0-D
X3-Hybrid-
12.0K-D
X3-Hybrid-
15.0-D
X3-Hybrid-
5.5-D LV
X3-Hybrid-
8.3-D LV
Battery type Lithium-ion battery / Lead-acid battery
Battery voltage
range [d.c. V]
120-800* 180-650
Max. continuous
charge/
discharge
current [d.c. A]
30 A
Communication
interface
CAN/RS485
Reverse
connection
protection
Yes
*
Compatible with a minimum of 3 units of HS25/HS36 batteries, but if the total voltage of the 3 batteries is less than 127V
and there is no PV input, the system will be not able to start.