Operation on LCD
»
Peak Shaving: When the power consumption from the grid exceeds the
set PeakLimits value, the battery is allowed to discharge power. The excess
power beyond the limit is provided by the combination of photovoltaic and
battery to ensure that the maximum power purchased from the grid does
not exceed the set limit. When the current working mode is peak shaving,
you can view the set PeakLimits.
========TOU========
Current Mode
Peak Shaving
========TOU========
>PeakLimits
1000W
»
Charging: The power of PV will charge the battery as much as possible to
the set SOC of Charge BAT to (%). When the battery reaches the set SOC, the
surplus power will perform Self-use mode or supply to the grid ( based on
the system setup), at this point, Charge from grid is not allowed. When the
current working mode is Charging, you can view the target charging SOC.
========TOU========
Current Mode
Charging
========TOU========
>Charge from grid
Enable
========TOU========
>Charge BAT to
50%
»
Discharging: If allowed by the battery, the system outputs a specified power
from the grid based on the set output percentage, controlling the power
at the AC terminal. You need to set the RatePower (%) through Web or
App when choosing Discharging mode. When the battery Discharge to (%)
reaches the set SOC, the inverter performs Self-use mode. You can view the
Rate of AC Power and Discharge to (%) here.
========TOU========
Current Mode
Discharging
========TOU========
>Rate of AC Power
100%
========TOU========
>Discharge to
10%
10.6 System Status
Displaying path: Menu>System Status
After entering into the System Status interface, the status of PV, Battery, On-grid, EPS,
Meter/CT will be displayed on the LCD as follows:
• PV: Information of PV1 and PV2 contains input voltage, current and power of
each PV.
====System Status====
>PV1
PV2
========PV1========
>U 0.0V
I 0.0A
P 0W