17
Product Overview
ChargePowerLimits: The charging power from grid. 1000 W by default, range is 0-60000
W.
PeakLimits: The load consumption power from grid side. 0 W by default, range: 0-60000
W.
Reserved SOC: The lower limit of battery SOC required for later peak shaving period. 50%
by default, range is 10~100%.
2.7.5 TOU Mode
In TOU mode, different working modes, i.e Self-use, Feed-in Prioirty, Peak shaving,
Charging, Discharging and battery off can be set for different time slots in accordance with
actual needs and environment conditions through SolaX Cloud App or Web.
The day can be divided into up to 10 time slots, and the minimum time slot is 15 minutes,
independent working mode can be set for each time slot. Please refer to web guide or App
guide for details about how to set the TOU mode.
Table 2-8 Time slot set
Time Slot Working Mode
x:xx~x:xx
(e.g 0:00~0:15 )
Choose one mode from Self-use / Feed-in Prioirty / Peak shaving /
Charging / Discharging / Battery off
Note:
Self-use: Same working logic with "2.7.1 Self-use Mode", but it is not limited by the charging
and discharging period.
Feed-in Prioirty: Same working logic with "2.7.2 Feed-in Priority", but it is not limited by the
charging and discharging period.
Peak shaving: The working logic is that when the power consumption from the grid
exceeds the set PeakLimits value, the battery is allowed to discharge power. The excess
power beyond the limit is provided by the combination of photovoltaic and battery to
ensure that the maximum power purchased from the grid does not exceed the set limit.
You need to set the PeakLimits value through Web or App when choosing Peak shaving
mode.
Charging: If allowed by the battery, the system charges the battery from the grid with a
specified power based on the set output percentage, controlling the power at the AC
terminal. You need to set the RatePower (%) through Web or App when choosing Charging
mode.
Discharging: If allowed by the battery, the system outputs a specified power from the grid
based on the set output percentage, controlling the power at the AC port. You need to set
the RatePower (%) through Web or App when choosing Discharging mode.
Battery off: The battery neither charges nor discharges power. The power of PV will supply
to loads or feed into the grid. Only when the battery SOC is lower than the system (TOU)
Min SOC, the battery can be charged.