15.1.3 ATS Control Mode
In this operating mode, the generator functions as a substitute for the grid. There is
no communication between the generator and the inverter, which means no wiring
modifications are required (although the inverter cannot control the generator). The ATS
working for the generator determines whether the generator should be turned on or off
based on the status of the grid.
Wiring connection diagram
EPS (off-grid) loads GeneratorCommon loads
Meter
Grid
PV
Cloud
AC
DC
COM
CT
ATS
Figure 15-1 ATS control wiring diagram
Inverter settings for ATS control mode
a. Select Menu>Setting>Advance Setting>ExternalGen>ATS Control.
=====ExternalGen=====
>Function Control
ATS Control
b. Set the relative parameters as below in accordance with actual needs.
»
MaxChargePower: Default: 5000 W, range: 0-300000 W
Maximum battery charging power from generator.