147
Appendix
15.4.4 Settings for DataHub
a. Select Menu>Setting>Advance Setting>Modbus;
b. Select the DataHub and set the Baud Rate and corresponding Address.
=======Modbus=======
>Function Control
Datahub
=======Modbus=======
>Baud Rate
9600
=======Modbus=======
>Datahub Addr:
1
NOTICE!
The baud rate, communication protocol and verification method of the inverters
connected to the same RS485 terminal of DataHub must be consistent, and the
communication addresses of the inverters must be consecutive and not repeated.
NOTICE!
For specific wiring and setting procedures of DataHub, see DataHub 1000 user
manual.