93
Operation on LCD
=====User Setting=====
Peak shaving mode
>Dry Contact
User PassWord
=====Dry Contact=====
Load Management
>Generator
Setting User Password
The default password is "0 0 0 0". You can reset the password here.
10.8.2 Advanced Setting
Setting path: Menu>Setting>Advance Setting
NOTICE!
• All the adjustable parameters including safety code, grid parameter, export control,
etc. can be modified under the permissions of installer password. Unauthorized use
of the installer password by unauthorized persons can lead to incorrect parameters
being inputted, resulting in power generation loss or violation of local regulation. Get
the installer password from the dealer and never open the password to unauthorzied
person.
Setting Safety Code
NOTICE!
• The inverter cannot be connected to the grid before the safety code is correctly set. If
there is any doubt about your safety code where the inverter installed, please consult
your dealer or SolaX service for details.
• The setup will vary from different saftey codes.
Here you can set safety code according to different countries and grid-tied standards. In
addition, the inverter has an User Defined option which allows you to customize relevant
parameters with a wider range.
There are several standards to choose from, please refer to the LCD screen on the inverter.
For Australia, select Australia Region A / B / C in complicance with AS/NZS 4777.2. Only
after the safety code setting is completed, some designated parameters in the inverter
system will take effect according to the corresponding safety regulations.
Table 10-3 Region settings
Region Australia A Australia B Australia C
New
Zealand
Standard
Code Name
AS4777_2020
_A
AS4777_2020
_B
AS4777_2020
_C
New
Zealand
Setting
Range
OV-G-V 265 V 265 V 265 V 265 V 230-300 V