94
Operation on LCD
Region Australia A Australia B Australia C
New
Zealand
Standard
Code Name
AS4777_2020
_A
AS4777_2020
_B
AS4777_2020
_C
New
Zealand
Setting
Range
OV-GV1-T 1.5 s 1.5 s 1.5 s 1.5 s
OV-G-V2 275 V 275 V 275 V 275 V 230-300 V
OV-GV2-T 0.1 s 0.1 s 0.1 s 0.1 s
UN-G-V1 180 V 180 V 180 V 180 V 40-230 V
UNGV1-T 10 s 10 s 10 s 10 s
UN-G-V2 70 V 70 V 70 V 70 V 40-230 V
UNGV2-T 1.5 s 1.5 s 1.5 s 1.5 s
OV-G-F1 52 Hz 52 Hz 55 Hz 55 Hz 50-55 Hz
OVGF1-T 0.1 s 0.1 s 0.1 s 0.1 s
OV-G-F2 52 Hz 52 Hz 55 Hz 55 Hz 50-55 Hz
OVGF2-T 0.1 s 0.1 s 0.1 s 0.1 s
UN-G-F1 47 Hz 47 Hz 45 Hz 45 Hz 40-50 Hz
UNGF1-T 1.5 s 1.5 s 5 s 1.5 s
UN-G-F2 47 Hz 47 Hz 45 Hz 45 Hz 45-50 Hz
UNGF2-T 1.5 s 1.5 s 5 s 1.5 s
Startup-T 60 s 60 s 60 s 60 s 15-1000 s
Restore-T 60 s 60 s 60 s 60 s 15-600 s
Recover-VH 253 V 253 V 253 V 253 V
Recover-VL 205 V 205 V 205 V 198 V
Recover-FH 50.15 Hz 50.15 Hz 50.15 Hz 50.15 Hz
Recover-FL 47.5 Hz 47.5 Hz 47.5 Hz 47.5 Hz
Start-VH 253 V 253 V 253 V 253 V
Start-VL 205 V 205 V 205 V 198 V
Start-FH 50.15 Hz 50.15 Hz 50.15 Hz 50.15 Hz
Start-FL 47.5 Hz 47.5 Hz 47.5 Hz 47.5 Hz