144
Appendix
15.3.4 Setting for EV-Charger
a. Select Menu>Setting>Advance Setting>Modbus;
b. Select the EV Charger and set the Baud Rate and corresponding Address. The
default Baud Rate is 9600.
=======Modbus=======
>Function Control
EV Charger
=======Modbus=======
>Baud Rate
9600
=======Modbus=======
>EV Charger Addr:
70
NOTICE!
• When EV-Charger and other communication device need to be connected at the
same time, the Baud rate of the two equipments shall be set to the same.
c. Check the connection status.
=======Modbus=======
>EV Charger COM STAT
Connected
d. You can enable Battery Charge EVC to allow the battery to discharge energy
to EV-Charger through setting path: Menu>Setting>Advance Setting>Battery
Charge EVC.
===Battery Charge EVC===
>Function Control
Enable
NOTICE!
• For specific wiring and setting procedures of EV-Charger, see X1/X3-EVC series user
manual.