27
Preparation before Installation
5.1.2 Installation Carrier Requirement
The installation carrier must be made of a non-flammable material, such as solid brick,
concrete, etc. and be capable of supporting the weight of the inverter and suitable of the
dimensions of the inverter
.
If the wall strength is not enough (such as wooden wall, the
wall covered by a thick layer of decoration), it must be strengthened additionally.
Fire resistant
Withstand four times
inverter's weight and be
suitable for installation
and dissipation
Figure 5-3 Installation carrier requirement
Table 5-2 The weight of inverters
Model
5.0 kW 6.0 kW 8.0 kW
10.0 kW
5.5 kW
12 kW
8.3 kW
15 kW
Weight 30±1 kg
NOTICE!
• Please take the weight of battery into account when wall-mouting the whole system.
5.1.3 Clearance Requirement
The minimum clearance reserved for the connected terminal at the bottom of inverter
should be 120 mm. When planning installation space, it is important to consider the
bending radius of the cables.
To guarantee proper heat dissipation and ease of disassembly, the minimum space around
the inverter must meet the standards indicated below.
For installations with multiple inverters, make sure to leave a minimum space of 300
mm between left and right inverter and 1000 mm between upper and lower inverter. In
areas with high ambient temperatures, increase the clearances between the inverters and
provide adequate fresh air ventilation if feasible.