138
Appendix
»
MinRestTime: Minimum time interval for two consecutive starts to avoid
frequent generator on and off. (60 Min by default)
=====ExternalGen=====
>MaxRestTime
0Min
»
Char&Disc Period: Including Forced Charg Period and Allowed Disc Period.
Two periods can be set. These period settings are associated with the same
settings under Working mode for no need to jump to working mode page to
set the working period when using generator mode.
=====ExternalGen=====
>Forced Charg Period
Start Time
00:00
=====ExternalGen=====
>Forced Charg Period
End Time
00:00
=====ExternalGen=====
>Allowed Disc Period
Start Time
00:00
=====ExternalGen=====
>Allowed Disc Period
End Time
00:00
»
Allow Work: Allowed time period for generator operating. You can set the
start time and end time.
=====ExternalGen=====
>Allow Work
Start Time
00:00
=====ExternalGen=====
>Allow Work
End Time
00:00
»
Charge from Gen and Charge battery to:
Charge battery to: Default: 10%; range: 10-100%
The SOC which allows the system charging from generator.
=====ExternalGen=====
Charge from GEN
> Enable <
=====ExternalGen=====
>Charge battery to
10%
»
HoldGenMinPower: Default: 0 W; range: 0-60000 W
The minimum charging power of the generator to charge the battery.
=====ExternalGen=====
HoldGenMinPower
0 W