Operation on LCD
»
It can be used in specific time period. In this period, the inverter does not
allow taking grid energy to charge the battery. PV is the only way to charge
the battery and PV will charge the battery first. Inverter will not supply power
to loads until battery SOC is higher than the Reverved_SOC in order to save
enough energy for later shaving period.
==Peak shaving mode==
>Reserved_SOC
===ReservedSOC===
Reserved SOC
> 50% <
Dry contact
Load management
This function is applicable for the first generation of SolaX Adapter Box.
a. Enter the Load Management interface through the path: Menu>Setting>User
Setting>Dry Contact>Load Management.
=====User Setting=====
Peak shaving mode
>Dry Contact
User PassWord
=====Dry Contact=====
>Load Management
Generator
b. Set the Load Management mode. Overall three heat pump operation modes are
available for you to choose:
===Load Management===
>Mode Select
Disable
===Load Management===
>Mode Select
Manual
===Load Management===
>Mode Select
SmartSave
»
Mode 1 Disable: The Adapter Box function is disabled under this operation
mode.
»
Mode 2 Manual: In this operating mode, you can change the Adapter Box
from on to off, or from off to on through settings on the inverter or through
SolaX App.
»
Mode 3 SmartSave: In this operating mode, users can set a series of
parameters on the SolaX inverter to intelligently control how and when the
heat pump works for them (see Step C).
c. Set the parameters for mode SmartSave. In this mode, you can set Thresholds
on Feedin power, Thresholds off Consumption, Thresholds off Battery SOC,
Mnimum duration per on-signal, Minimum duration per day and Schedule in
accordance with your actual needs.