=====ExternalGen=====
>Start Gen Method
Reference soc
=====ExternalGen=====
>Start Gen Method
Immediately
»
Switch on/off SOC: the option is activated when you select Reference SOC
for Start Gen Method. Inverter will turn on the generator when the battery
reaches the set Switch on SOC and turn it off when the battery reaches the
set Switch off SOC.
=====ExternalGen=====
>Switch on SoC
0%
=====ExternalGen=====
>Switch off SoC
0%
»
MaxRunTime: Maximum operating time of generator. (30 Min by default)
=====ExternalGen=====
>MaxRunTime
30Min
»
MinRestTime: Minimum time interval for two consecutive starts to avoid
frequent generator on and off.
=====ExternalGen=====
>MaxRestTime
0Min
»
Char&Disc Period: Including Forced Charg Period and Allowed Disc Period.
Two periods can be set. These period settings are associated with the same
settings under Work Mode for no need to jump to work mode page to set
the working period when using generator mode.
=====ExternalGen=====
>Forced Charg Period
Start Time
00:00
=====ExternalGen=====
>Allowed Disc Period
Start Time
00:00
=====ExternalGen=====
>Forced Charg Period
End Time
00:00
=====ExternalGen=====
>Allowed Disc Period
End Time
00:00
»
Allow Work: Allowed time period for generator operating. You can set the
start time and end time.
=====ExternalGen=====
>Allow Work
Start Time
00:00
=====ExternalGen=====
>Allow Work
End Time
00:00
»
Charge from Gen and Charge battery to: The SOC which allows the system
charging from generator. (10-100 W from generator, 10% by default)